Note: In some applications such as fire insulation solutions local regulations must be considered.
Insulation of ducts installed against partitioning structures
When the distance of duct from structure is over 30 mm, but does not exceed insulation thickness:
|

|
1. > 30 mm < s
2. < 100 mm
3. s
4. appr. 100 mm
5. appr. 100 mm
6. PAROC Wired Mat or PAROC Fire Slab
7. Partitioning structure |
When the distance of duct from the structure is max. 30 mm:
|

|
1. < 30 mm
2. appr. 100 mm
3. appr. 100 mm
4. Welding bolts with fixing plates > 6 pcs/m2 |
Insulation that partly surrounds a duct can be fastened to the partitioning structure using a steel section support:
|

|
1. PAROC Wired Mat
2. Steel section support
3. Partitioning building structure |
Support of wire net mat insulation in vertical duct
In vertical ducts, adequate vertical support prevents the wire net mat from compressing, use steel wire and/or supporting collars fixed to the net and the structures. The distance between the vertical supports should not exceed normal floor height (appr. 3 m).
|

|
1. PAROC Wired Mat
2. Support of insulation against structure
3. Collar, flange, spikes or corresponding support of insulation
4. Distance between supporting
points < 2700 mm (= three mat widths) |
> Fastening a wire net mat with steel wire or clips
Insulation of round duct with stone wool pipe section
> Installation of uncoated pipe sections